Jim 'Slim' Mimlitz

Jim ‘Slim’ Mimlitz, SCADAmetrics

Connecting an Elster-AMCO (ABB-Kent) ScanCoder water meter register to an EtherMeter is straightforward.

ABB_ScanCoder_001

Just follow these simple steps:

1. Expose the communication wires by cutting the cable short of the ERT communication adapter:

ABB_ScanCoder_002

2. Strip away a couple inches of outer cable jacket, exposing the three inner conductors, and connect them to the EtherMeter.  When using meter channel #1, connect according to the following key: BLACK (Terminal 14), RED (Terminal 15), BARE-SHIELD (Terminal 16).

Alternatively, when using meter channel #2, connect according to the following key: BLACK (Terminal 17), RED (Terminal 18), BARE-SHIELD (Terminal 19).

Apply power to the EtherMeter, and watch the EtherMeter auto-detect the meter register:

ABB_ScanCoder_003

Jim 'Slim' Mimlitz

About Jim 'Slim' Mimlitz

Licensed Professional Electrical Engineer @ SCADAmetrics. Specialties: Connecting Flow Meters with SCADA, Telemetry, and Building Automation Systems. Electronic Circuit Design, Software Development.

Leave a Reply

Post Navigation